Send Message

High Reliability 40.5KV Outdoor Vcb High Voltage 50 60 Rated Frequency

Basic Information
Place of Origin: Zhejiang, China
Brand Name: XK
Certification: ISO9001 / GB / IEC
Model Number: ZW7A-40.5
Minimum Order Quantity: 1 Piece/Pieces
Price: Negotiation
Packaging Details: EXPORTING PACKING
Supply Ability: 100 Piece/Pieces per Month
Name: Vacuum Circuit Breaker Standard: IEC
Rated Current: 1250A, 1600A Rated Voltage: 40.5KV
Mechanical Life: 10000 Port: NINGBO
High Light:

vcb circuit breaker

,

outdoor vcb breaker

High reliability 40.5KV outdoor high voltage  vacuum circuit breaker

Product Description

 

 

Item Unit Data
Rated frequency Hz 50,60
Power frequency with stand voltage 1min(wet)(dry) phase to ground/fracture KV
80 95/95
Lightning impulse with stand voltage KV 185
Rated short circuit breaking current KA 25/31.5
Rated short circuit witch ingcurrent KA 63/80
Rated peak with stand current KA 63/80
4S short time with stand current KA 25/31.5
Rated short circuit breaking times times
30
Control voltage of mechanism V AC/DC 220
Second ary circuit power frquency with stand voltage 1min KV 2
Contact opening distance mm 18±1
Contact over-travelling distance mm 4±0.5
Opening speed m/s 1.4-1.8
Closing speed m/s 0.4-0.8
Contact closing bounce time ms ≤5
Middled is tance between phases mm 700±2
Closing/Opening time difference between three phases ms ≤2
The circuit esistance of each phase Ω <80
Closing time ms ≤100
Opening time ms ≤50
Weight KG 500

High Reliability 40.5KV Outdoor Vcb High Voltage 50 60 Rated Frequency 0 

   

All circuit breaker systems have common features in their operation, but details vary substantially depending on the voltage class, current rating and type of the circuit breaker.

The circuit breaker must first detect a fault condition. In small mains and low voltage circuit breakers, this is usually done within the device itself. Typically, the heating or magnetic effects of electric current are employed. Circuit breakers for large currents or high voltages are usually arranged with protective relay pilot devices to sense a fault condition and to operate the opening mechanism. These typically require a separate power source, such as a battery, although some high-voltage circuit breakers are self-contained with current transformers, protective relays, and an internal control power source.

Once a fault is detected, the circuit breaker contacts must open to interrupt the circuit; this is commonly done using mechanically stored energy contained within the breaker, such as a spring or compressed air to separate the contacts. Circuit breakers may also use the higher current caused by the fault to separate the contacts, such as thermal expansion or a magnetic field. Small circuit breakers typically have a manual control lever to switch off the load or reset a tripped breaker, while larger units use solenoids to trip the mechanism, and electric motors to restore energy to the springs.

The circuit breaker contacts must carry the load current without excessive heating, and must also withstand the heat of the arc produced when interrupting (opening) the circuit. Contacts are made of copper or copper alloys, silver alloys and other highly conductive materials. Service life of the contacts is limited by the erosion of contact material due to arcing while interrupting the current. Miniature and molded-case circuit breakers are usually discarded when the contacts have worn, but power circuit breakers and high-voltage circuit breakers have replaceable contacts.

When a high current or voltage is interrupted, an arc is generated. The length of the arc is generally proportional to the voltage while the intensity (or heat) is proportional to the current. This arc must be contained, cooled and extinguished in a controlled way, so that the gap between the contacts can again withstand the voltage in the circuit. Different circuit breakers use vacuum, air, insulating gas, or oil as the medium the arc forms in. Different techniques are used to extinguish the arc including:

Lengthening or deflecting the arc
Intensive cooling (in jet chambers)
Division into partial arcs
Zero point quenching (contacts open at the zero current time crossing of the AC waveform, effectively breaking no load current at the time of opening. The zero-crossing occurs at twice the line frequency; i.e., 100 times per second for 50 Hz and 120 times per second for 60 Hz AC.)
Connecting capacitors in parallel with contacts in DC circuits.
Finally, once the fault condition has been cleared, the contacts must again be closed to restore power to the interrupted circuit.

Contact Details
Liu

Phone Number : +8613587461262