Indoor Vacuum Circuit Breaker / 1250A 1600A 11kv Vcb Panel Three Phase

Basic Information
Place of Origin: Zhejiang, China
Brand Name: XK
Certification: ISO9001 / GB / IEC
Model Number: ZN63-12KV/630A
Minimum Order Quantity: 1 Piece/Pieces
Price: Negotiation
Packaging Details: EXPORTING PACKING
Supply Ability: 100 Piece/Pieces per Month
Standard: GBJ, JB,IEC Rated Current: 630A,1250A, 1600A
Rated Voltage: 12KV Mechanical Life: 10000
Port: NINGBO
High Light:

vcb circuit breaker

,

outdoor vcb breaker

XK Indoor Vacuum circuit breaker, 11KV, High Quality Good Price

High quality 24KV Indoor three-phase ac 50-60HZ vacuum circuit breaker

Product Description

   Indoor Vacuum Circuit Breaker / 1250A 1600A 11kv Vcb Panel Three Phase 0

 

Operating Mechanism of Vacuum Circuit Breaker:

The lower end of the breaker is fixed to a spring-operated or solenoid operated mechanism so that the metallic bellows inside the chamber are moved upward and downward during closing and opening operations respectively. The contact movement should be such as to avoid bounce. It is noteworthy that the operating mechanism should provide sufficient pressure for a good connection between the contacts.

The pressure in a vacuum interrupter at the time of sealing off is kept about 10–6 torr. The interrupting rating is between 250 and 1,000 MVA. The normal current carrying capacity for a single interrupter is 800 – 3,000 A; 4.2 kV – 7.6 kV.

Item Unit Data
Rated voltage KV 12
Maximum working voltage KV 12
Rated Current A 630-1250 630-1600 630-1600
Rated short circuit breaking current KA 20 25 31.5
Rated short-circuit switching current KA 50 63 80
Rated peak withstand current KA 50 63 80
4S rated short-circuit withstand current KA 20 25 31.5
Rated insulation level 1min Power frequency withstand voltage KV 42(fracture 48)
lmpulse withstand voltage KV 75(fracture 84)
Rated short-circuit current breaking times Times 50
Rated Operating Mechanism Closing Voltage(DC) V AC,DC 110,220
Rated Operating Mechanism Opening Voltage(DC) V AC,DC 110,220
Contact opening distance mm 11±1
Overtravel(the length of contact spring compression) mm 3.5±0.5
Closing/Opening Time Difference Among Three Phase ms 2
Contact closing bounce time ms 2
Average opening speed m/s 0.9-1.2
Average closing speed m/s 0.5-0.8
Tripping Time Maximum operating voltage S ≤0.05
Minimum operating voltage S ≤0.08
Closing time S 0.1
The main circuit resistance of each phase   630≤50 1250≤45 1600≤40
Allowed Consumpted thickness of Contacts mm 3